Showing posts with label Telemacanique. Show all posts
Showing posts with label Telemacanique. Show all posts

Thursday, 30 May 2019

Telemecanique Altistart 01 repair

Hari ini saya dirujuk sesuatu yang baru berjenama Telemecanique, Model: ATS01N212QN dan anda boleh melihatnya pada gambar di bawah.
Jenama: Telemecanique, Model: Altistart 01
Saya diberitahu masalahnya ialah ianya tidak berfungsi walaupun lampu indicator berwarna hijau dan kuning menyala.
Sebiji kapasitor didapati rosak...
Setelah diperiksa menyeluruh, hanya sebiji kapasitor sahaja yang didapati nilainya telah berkurangan hampir 50% seperti boleh anda lihat pada gambar di atas dan bawah.
Kapasitor lama 24.3uF sahaja...
Kapasitor baru 47.6uF...
Setelah kapasitor tersebut ditukar dan diuji, kini ianya boleh digunakan semula.
Kapasitor yang lama telah diganti baru...
Selamat mencuba...

Wednesday, 25 April 2018

How to setup preset speeds on an Telemecanique Altivar 11


Telemecanique Altivar 11

There are two ways of setting and depends on the application, the one most commonly used is as follows:

You set you lowest speed into LSP and then assign the inputs you are using to give you your preset speeds (LI3 and LI4). LI1 is run forward and LI2 is run reverse, so when LI1 is high (+24v) the motor will run forward at the speed set in LSP, the same will happen when LI2 is high except the motor will run reverse. With the run signal on either LI1 or LI2 and LI3 high the motor will run FWD/REV at the second speed (SP2), if LI1 or LI2 and LI4 are high the motor will run at the third speed (SP3). The fourth speed (SP4) is attained by making LI1 or LI2 high and both LI3 and LI4 high as well. So here is the way to set this up (the figures used are just for examples, you will need to set your own)

Firstly set LSP to 10Hz and HSP to 50Hz (or motor maximum frequency)
then scroll down till you see FUN and then press enter
from here press the down arrow until rrS and press enter
set rrS to LI2 this has enabled reverse onto LI2
scroll down to PS2 and press enter
set LIA to LI3
then LIB to LI4
next set SP2 to 30Hz
SP3 to 40Hz
and SP4 to 50Hz

With 24 volts on LI1 motor speed is 10Hz

With 24 volts on LI1 and LI3 motor speed is 30Hz

With 24 volts on LI1 and LI4 motor speed is 40Hz

With 24 volts on LI1, LI3 and LI4 the motor speed is 50hz

In reverse direction LI1 is replaced by LI2

The second option is to short out +5 to AI1 so the drive starts at maximum speed then by introducing the different logic inputs the preset speeds are called for. The only difference in the programming is that

LSP is set to 0Hz

and SP4 set to 10Hz

With 24 volts on LI1 motor speed is 50Hz

With 24 volts on LI1 and LI3 motor speed is 30Hz

With 24 volts on LI1 and LI4 motor speed is 40Hz

With 24 volts on LI1, LI3 and LI4 the motor speed is 10hz

In reverse direction LI1 is replaced by LI2

One problem with this option is if you lose the preset speed signals the drive will revert to full speed.

Friday, 13 April 2018

How to reset Telemecanique Altivar 11 (ATV11HU29M2A) back to factory defaults

 
1. Turn on the soft starter

2. go to FUN menu + enter
3. look for FCS + enter
4. Change NO to Inl and
5. press enter key and hold for about 2 seconds.